RC Series

GENSET MODEL

ESP
kVA/kW

PRP
kVA/kW

ENGINE MODEL

CYL.

PDF

DESIGN SPECIFICATIONS;High quality, reliable and complate power unit,Compact design,Easy start and maintenance possibility,Every generating set is subjected to a comprehensive test programme which includes full load testing and checking and providing of all control and safety shut down functions testing,Full engineered with a wide range of options and accessories:Canopy,soundproof and on road trailerENGINE;CUMMINS heavy duty diesel engine,Four stroke, water cooled, 1500 rpm, turbocharged, charge air cooled  Direct injection fuel system, 24 VDC starter and charge alternator, Replaceable fuel filter, oil filter and dry element air filter,
Cooling radiator and fan,Starter battery (with lead acid) including Rack and Cables, Flexible fuel connection hoses and oil sump drain valve,
Industrial capacity exhaust silencer and steel bellows,Jacket water heater (at automatic models) Operation mauals and circuit diagram documents

ALTERNATOR;Brushless, single bearing system, 4 poles,Insulation class H,Standard degree of protection IP21,Self-exciting and self-regulating,Impregnation with tropicalised epoxy varnish,Solid state Automatic Voltage Regulator

BASE FRAME;The complete genset is mounted as whole on a heavy-duty fabricated, steel base frame. Antivibration pads are fixed between the engine/ alternator feet and the base frame. Base frame design incorporates an integral fuel tank. The generating set can be lifted or carefully pushed / pulled by the base frame,Lifting eyes allow easy transportation by a crain.
Dial type fuel gauge and drain plug on the fuel tank.

CANOPY;All canopy parts are designed with modular principles. without welding assembly. Doors on each side. All metal canopy parts are painted by electrostatic.  Exhaust silencer is protected against environment influencespolyester  powder paint.  Thermally insulated engine exhaust system. Emergency stop push button is installed outside of canopyEasy lifting and moving Easy mainteneance and operation

RC55

55

44

50

40

S3.8G5

4L

 
RC70

70

56

63

50.4

S3.8G7

4L

 
RC110

110

88

100

80

6BTA5.9-G5

6L

 
RC175

175

140

158

126

6BTAA5.9-G5

6L

 
RC200

200

160

180

144

6CTA8.3-G2

6L

 
RC250

250

200

225

180

6CTAA8.3-G2

6L

 
RC350

350

280

316

252

QSL9-G5

6L

 
RC400

400

320

356

284

NTA855-G4

6L

 
RC440

440

352

400

320

NTA855-G7

6L

 
RC515

515

412

460

368

QSX15-G6

6L

 
RC550

550

440

500

400

QSX15-G8

6L

 
RC703

703

562

638

510

VTA28-G5

12V

 
RC825

825

660

750

600

VTA28-G6

12V

 
RC880

880

704

800

640

QSK23-G3

6L

 
RC1100

1100

880

1000

800

QST30-G4

12V

 
RC1410

1410

1128

1280

1024

KTA50-G3

16V

 
RC1675

1675

1340

1500

1200

KTA50-G8

16V

 
RC2250

2250

1800

2000

1600

QSK60-G4

16V

 
RC2500

2500

2000

2000

1600

QSK60-G13

16V

 
ESP : Applicable for supplying power to varying electrical load for the duration of power interruption of a reliable utility source. ESP is in accordance with ISO 8528. Overload is not allowed.PRP :Applicable for supplying power to varying electrical load for unlimited hours.